23InRow SC Operation
Event Log
The event log saves status information and a message each time a change in the cooling unit is detected.
Alarms events are recorded in the log and displayed on the active alarm screens. Status (informational)
events and system configuration changes are only displayed in the event log. The number of messages in
the event log is limited to 500. When the number of messages in the event log reaches 500, the oldest
message will be dropped from the list every time a new message is added to the log.
View event log
Path: Main > View Event Log
The event log keeps a record of all alarms and events. The screen displays the following:
The name of the event
The time and date the event occurred
Use the arrow keys to scroll through the list of events and display the date and time for each event.
Clear event log
Path: Main > Clear Event Log
A confirmation screen is displayed when you select this option. Enter the Admin password to erase the
log. Select YES to erase all of the events in the log. Select NO to return to the main screen.
Respond to Alarms
When an alarm is triggered, the cooling unit alerts you through the display by the following methods:
Alarm screen entry on scrolling status screens
LEDs on the front panel display
An optional audible alarm every 30 seconds (if enabled)
View alarms
Path: Main > View Alarms
The View Alarms screen provides the number of alarms, the severity, and a brief description of the
alarm. Press the arrow keys to view the rest of the list.
Clear active alarms
Path: Main > Clear Alarms
A confirmation screen is displayed when you select this option. Enter the Admin password to clear the
alarm list. Select YES to clear all of the alarms in the list. Select NO to return to the main screen. If the
conditions that caused the alarm still exist, those conditions cause the alarm to be regenerated.
Note: A Critical fault prevents the system from performing its primary function. A primary
function is defined as any function that can effect the ability to deliver rated cooling
performance. A Warning fault is a fault that is not critical.