21InRow SC Operation
View Status Readings
The display interface has several options for viewing the status of the cooling unit, the cooling group to
which the cooling unit belongs, and the environment being controlled. The status readings for the
cooling unit are available under the View Unit Status option in the main menu, and status readings for
the cooling group are available under the View Group Status option on the main menu or on the
scrolling status screens.
Scrolling status screens
When the display interface is idle, it scrolls through screens of status information. Press the up or down
arrow key to interrupt the automatic scrolling and view a specific status screen.
Cooling unit status
Path: Main > View Unit Status
Op Mode.
The cooling unit is in one of the following modes:
On: The cooling unit is cooling.
Standby: The cooling unit is receiving power but is not enabled for cooling.
Idle: The cooling unit is on, but the compressor is not running because it has active alarms.
Cool Output. The actual cooling output of the cooling unit.
Cool Demand. The amount of cooling that the heat load currently requires.
Rack Inlet. The temperature of the air entering the rack at the remote temperature sensor.
Supply Air. The temperature of the air leaving the cooling unit.
Return Air. The temperature of the air entering the cooling unit.
Cond Outlet. The temperature of the air leaving the condenser.
Cond Inlet. The temperature of the air entering the condenser.
Suction Temp. The temperature of the low pressure refrigerant line.
Air Flow. The amount of air flowing through the evaporator required to maintain the setpoint
temperature.
Evap Fan Spd. The speed of the fans that regulate the air flow through the evaporator.
Cond Fan Spd. The speed of the fans that regulate air flow through the condenser.
Input State. The actual state of the input contact (open or closed).
Output State. The actual state of the output contact (open or closed).
Filter DP. The filter differential pressure.
Suction. The pressure at the compressor inlet.
Discharge. The pressure at the compressor outlet.
Superheat. The difference between the Suction Temp and the evaporator dew point temperature
Compressor. The state of the compressor, either on or off.