of 152
 
33NetBotz Appliance User’s Guide
Default alert profile
Your appliance comes pre-configured with a default alert profile. The default policy features the
following four pre-configured Alert Sequences which are active 24 hours a day, 7 days a week:
Alert Level 1: Begins immediately after an alert condition occurs (Start Value of 0) and repeats
two times at 5 minute intervals. It initiates the Primary E-Mail Notification, and Short Message
E-Mail alert actions.
Alert Level 2: Begins 20 minutes after an alert condition occurs and repeats one time at a 10
minute interval. It initiates the Secondary E-Mail Notification and Short Message E-Mail alert
actions.
Alert Level 3: Begins 90 minutes after an alert condition occurs and repeats two times at 60
minute intervals. It initiates the Primary E-Mail Notification, Secondary E-Mail Notification, and
Short Message E-Mail alert actions.
Continuous Alert: Begins immediately after an alert condition occurs (Start Value of 0) and
repeats indefinitely at one minute intervals. It initiates the Send SNMP Trap alert action.
Note: Pre-defined alert actions or individual sensor thresholds may require additional
information such as e-mail addresses, server IP addresses, output devices, etc., for
notifications to be delivered. Be sure to properly configure alert actions and thresholds
used in your Alert Profile.
The default alert profile can be edited but not removed. When sensor thresholds are created, the default
alert profile is used unless you use advanced threshold settings to specify otherwise. You can also create
additional Alert Profiles.
Creating or editing an alert profile
To create a new alert profile or modify an existing alert profile:
1. Double-click the Alert Profile icon.
2. Click Add....
3. Type a label for the Alert Profile and configure the Alert Sequence(s) for the new profile.
For information on creating an Alert Sequence, see “Creating an alert sequence” on
page 34.
4. Click the Advanced tab to schedule an alert notification delay, if desired.
5. If you are modifying an existing alert profile, select the alert profile from the Profile table and
click Edit.... When you finish making your changes, click OK.