InRow SC Operation16
Run hours
Path: Main > View Run Hours
The cooling unit records the number of hours each of its components has operated. When a component is
replaced, use the Reset option to reset the run hours for the displayed component to zero.
Path: Main > View Run Hours > Air Filter
Air Filter
Reset Run Hours
Path: Main > View Run Hours > Fans > Condenser
Fan n (n = 1, 2, or 3)
Reset Run Hours
Path: Main > View Run Hours > Fans > Evaporator
Fan n (n = 1, 2, or 3)
Reset Run Hours
Path: Main > View Run Hours > Compressor
Compressor
Reset Run Hours
Path: Main > View Run Hours > Condensate Pump
Conds Pump (Condensate Pump)
Reset Run Hours
Path: Main > View Run Hours > Fan Power Supplies
LT Fan PS (Left Fan Power Supply)
RT Fan PS (Right Fan Power Supply)
Reset LT PS Hours (Reset Left Fan Power Supply Hours)
Reset RT PS Hours (Reset Right Fan Power Supply Hours)
Thresholds
Set alarms to alert you when components require service or there are high temperature violations.
Path: Main > Set Unit Thresholds
When the air temperature exceeds the temperature defined by the High Temperature Threshold, an
alarm will occur. Set High Temperature Thresholds for the following:
Rack Inlet: An alarm condition exists when the temperature of the air entering the rack at the rack
inlet sensor exceeds the threshold.
Supply Air: An alarm condition exists when the temperature of the air output from the cooling
unit exceeds the threshold.
Return Air: An alarm condition exists when the temperature of the air entering the cooling unit at
the temperature sensor exceeds the threshold.